Flexible power cable, G10 rubber compound insulated, with special thermoplastic outer sheath, M1 quality, halogen-free, not propagating fire with low smoke emission.
Conductor
Plain copper flexible wire, class 5
Insulation
Rubber compound, G10 quality
Filler
Non-hygroscopic compound
Outer Sheath
LS0H compound, M1 quality
LS0H = Low Smoke Zero Halogen
Cores Colour
HD 308 Standard
Sheath Colour
Black
Technical Characteristics
Nominal voltage Uo/U: 0,6/1 kV
Maximum operating temperature: 90°C
Minimum operating temperature: -15°C
(without mechanical stress)
Minimum installation temperature: 0°C
Maximum short circuit temperature: 250°C
Maximum tensile stress: 50 N/mm2
Minimum bending radius: 4 x maximum external diameter
Minimum bending radius: 8 x maximum external diameter
Use and Installation
Suitable to be used in high density and high risk of fire places like offices, schools, theaters, discos etc.. To be used indoor and outdoor, even in wet environments, for fixed laying, in pipes and dumps, metal structures, masonry, underground. (ref. CEI 20-67)