ARE4*E4*X* – ARE4* 0,6/1 kV
Standard Reference
ENEL DC 4182 – ENEL DC 4908 | Construction & Specifications |
CENELEC HD 603 | |
2014/35/UE | Low Voltage Directive |
2011/65/CE | RoHS Directive |
ENEL-DIS-23/12/2014-1110670 | ENEL Certification |
ENEL DC 4182 – ENEL DC 4908 | Construction & Specifications |
CENELEC HD 603 | |
2014/35/UE | Low Voltage Directive |
2011/65/CE | RoHS Directive |
ENEL-DIS-23/12/2014-1110670 | ENEL Certification |
Four-core cable visible helix assembled for aerial installation, XLPE insulated, with self-supporting neutral central conductor made of aluminium alloy without sheath, and with phase aluminium conductors XLPE sheathed.
Phase Conductor
Aluminium stranded wire, class 2
Neutral Self-supporting Conductor
Aluminium alloy stranded wire, class 2
Phase and Neutral Conductor Insulation
Cross-linked polyethylene XLPE
Phase Conductor Sheath
Cross-linked polyethylene XLPE
Phase Conductor Insulation Colour
Black
Neutral Conductor Insulation Colour
Grey
Phase Conductor Sheath Colour
Grey
Nominal voltage Uo/U: 0,6/1 kV
Maximum operating temperature:
85°C (phase conductor), 65°C (neutral conductor)
Minimum installation temperature: 0°C
Minimum operating temperature: -15°C
(without mechanical stress)
Maximum short-circuit temperature:
250°C (phase conductor), 180°C (neutral conductor)
Maximum tensile stress: 680 kg total
Minimum bending radius: 18 x maximum external diameter
Suitable for low voltage power transportation with overhead lines; suitable to be installed on supports, in pipes or conduits, along the walls of buildings.