AUG7(E4*)CR – ARG7(E4*)CR 0,6/1 kV
Standard Reference
ENEL DC 4125 – ENEL DC 4908 | Construction & Specifications |
CENELEC HD 603 | |
2014/35/UE | Low Voltage Directive |
2011/65/CE | RoHS Directive |
ENEL-DIS-10/09/2014-0791663 | ENEL Certification |
ENEL DC 4125 – ENEL DC 4908 | Construction & Specifications |
CENELEC HD 603 | |
2014/35/UE | Low Voltage Directive |
2011/65/CE | RoHS Directive |
ENEL-DIS-10/09/2014-0791663 | ENEL Certification |
Two-core cable with aluminium solid conductor (AUG7/AUE4*) or stranded wire (ARG7/ARE4*), and concentric copper conductor, insulated with high-quality ethyl-propylene rubber (G7) or cross-linked polyethylene (E4*), with PVC sheath.
Conductor
Aluminium solid conductor, class 1 (section 10 mm²)
Aluminium stranded wire, class 2 (section 25 mm²)
Insulation
Rubber HEPR compound (G7) or cross-linked polyethylene XLPE (E4*)
Concentric Neutral Conductor/Screen
Annealed bare copper wires with copper tape wrapped contrariwise
Outer Sheath
PVC compound, Rz quality
Insulation Colour
Black
Sheath Colour
Grey
Nominal voltage Uo/U: 0,6/1 kV
Maximum operating temperature: 90°C (phase conductor), 85°C (concentric conductor)
Minimum installation temperature: 0°C
Minimum operating temperature: -15°C
(without mechanical stress)
Maximum short-circuit temperature: 250°C (phase conductor), 160°C (concentric conductor)
Maximum tensile stress: 50 N/mm2
Minimum bending radius: 14 x maximum external diameter
Suitable to be used indoor or outdoor, even in wet environments; it can be fixed on walls and/or metal structures. Suitable also for laying underground.