ARE4*E4*X 0,6/1 kV
Standard Reference
ENEL DC 4183 – ENEL DC 4908 | Construction & Specifications |
CENELEC HD 626 | |
2014/35/UE | Low Voltage Directive |
2011/65/CE | RoHS Directive |
ENEL-DIS-23/12/2014-1110652 | ENEL Certification |
ENEL DC 4183 – ENEL DC 4908 | Construction & Specifications |
CENELEC HD 626 | |
2014/35/UE | Low Voltage Directive |
2011/65/CE | RoHS Directive |
ENEL-DIS-23/12/2014-1110652 | ENEL Certification |
Two and four-core self-supporting cable visible helix assembled for aerial installation, with aluminium conductors XLPE insulated, with XLPE sheath.
Conductor
Aluminium stranded wire, class 2
Insulation
Cross-linked polyethylene XLPE
Sheath
Cross-linked polyethylene XLPE
Insulation Colour
Black
Sheath Colour
Grey
Nominal voltage Uo/U: 0,6/1 kV
Maximum operating temperature: 75°C
Minimum installation temperature: 0°C
Minimum operating temperature: -15°C
(without mechanical stress)
Maximum short-circuit temperature: 160°C
Maximum tensile stress:
250 kg for two-core cable; 500 kg for four-core cable
Minimum bending radius: 18 x maximum external diameter
Suitable for low voltage power transportation with overhead lines; suitable to be installed on supports, in pipes or conduits, along the walls of buildings.