ARG7R – ARG7OR 0,6/1 kV
Standard Reference
CEI 20-13 | Construction & Specifications |
CEI EN 60332-1-2 | Flame propagation |
CEI 20-22 II | Fire propagation |
CCEI EN 50267-2-1 | Gas emission |
2014/35/UE | Low Voltage Directive |
2011/65/CE | RoHS Directive |
CEI 20-13 | Construction & Specifications |
CEI EN 60332-1-2 | Flame propagation |
CEI 20-22 II | Fire propagation |
CCEI EN 50267-2-1 | Gas emission |
2014/35/UE | Low Voltage Directive |
2011/65/CE | RoHS Directive |
Description
Power cable with aluminium conductor, insulated with high-quality ethyl-propylene rubber G7, with PVC sheath, not propagating fire with reduced corrosive gas emission.
Conductor
Aluminium stranded wire, class 2
Insulation
Rubber HEPR compound G7 quality
Filler
Non-hygroscopic compound (for multi-core cables)
Outer Sheath
PVC compound, Rz quality
Cores Colour
HD 308 Standard
Sheath Colour
Grey
Technical Characteristics
Nominal voltage Uo/U: 0,6/1 kV
Maximum operating temperature: 90°C
Minimum operating temperature: -15°C
(without mechanical stress)
Minimum installation temperature: 0°C
Maximum short circuit temperature:
250°C up to 240 mm² section, over 220°C
Maximum tensile stress: 50 N/mm2
Minimum bending radius: 6 x maximum external diameter
Use and installation
Power cable for industrial and/or residential uses. Suitable to be used indoor or outdoor, even in wet environments; it can be fixed on walls and/or metal structures. Suitable also for laying underground.