AUG7(E4*)R – ARG7(E4*)R 0,6/1 kV

Standard Reference
ENEL DC 4152 – ENEL DC 4908 Construction & Specifications
CENELEC HD 603
2014/35/UE Low Voltage Directive
2011/65/CE RoHS Directive

Product Info

Product Description

Description

Power cable with aluminium conductor, insulated with high-quality ethyl-propylene rubber (G7) or cross-linked polyethylene (E4*), with PVC sheath.

Conductor
Aluminium solid conductor, class 1 (section 10 mm2)
Aluminium stranded wire, class 2 (section > 10 mm2)

Insulation
Rubber HEPR compound (G7) quality or cross-linked polyethylene (E4*)

Filler
Non-hygroscopic compound (for multi-core cables)

Outer Sheath
PVC compound, Rz quality

Insulation Colour
Black

Sheath Colour
Grey

Technical Characteristics

Nominal voltage Uo/U: 0,6/1 kV

Maximum operating temperature: 90°C
Minimum operating temperature: -15°C
(without mechanical stress)
Minimum installation temperature: 0°C

Maximum short-circuit temperature: 250°C
Maximum tensile stress: 50 N/mm2
Minimum bending radius: 6 x maximum external diameter

Use and installation

Suitable to be used indoor or outdoor, even in wet environments; it can be fixed on walls and/or metal structures. Suitable also for laying underground.