Description
Power cable insulated with high-quality ethyl-propylene rubber, G7 quality, with PVC sheath, not propagating fire with reduced corrosive gas emission.
Conductor
Plain copper flexible wire, class 5
Insulation
Rubber HEPR compound, G7 quality
Filler
Non-hygroscopic compound (for multi-core cables)
Outer Sheath
PVC compound, Rz quality
Cores Colour
HD 308 Standard
Sheath Colour
Grey
Technical Characteristics
Nominal voltage Uo/U: 0,6/1 kV
Maximum operating temperature: 90°C
Minimum operating temperature: -15°C
(without mechanical stress)
Minimum installation temperature: 0°C
Maximum short circuit temperature:
250°C up to 240 mm² section, over 220°C
Maximum tensile stress: 50 N/mm2
Minimum bending radius: 4 x maximum external diameter
Use and Installation
Suitable to be used indoor or outdoor, even in wet environments; it can be fixed on walls and/or metal structures, free in air, inside pipes or similar systems. Suitable also for laying underground. (ref. CEI 20-67)