Description
PVC insulated signalling and control cable with PVC sheath, not propagating fire with reduced corrosive gas emission.
Conductor
Plain copper flexible wire, class 5
Insulation
PVC compound, TI2 quality
Outer Sheath
PVC compound, TM2 quality
Cores Colour
Black numbered with yellow/green protection conductor
Sheath Colour
Grey
Technical Characteristics
Nominal voltage Uo/U: 300/500 V
Maximum operating temperature: 70°C
Minimum operating temperature: -15°C
(without mechanical stress)
Minimum installation temperature: 0°C
Maximum short circuit temperature: 160°C
Maximum tensile stress:
15 N/mm2 (mobile laying)
50 N/mm2 (fixed laying)
Minimum bending radius:
4 x maximum external diameter (fixed laying)
10 x maximum external diameter (mobile laying)
Use and Installation
Suitable for connection of movable equipment or for fixed laying in areas with risk of fire. To be used in dry or wet interiors and for occasional or temporary use outdoor. Not allowed for laying underground even if protected.