U/RG7R – U/RG7OR 0,6/1 kV

Standard Reference
CEI 20-13 – CEI UNEL 35376 Construction & Specifications
CEI EN 60332-1-2 Flame propagation
CEI 20-22 II Fire propagation
CEI EN 50267-2-1 Gas emission
2014/35/UE Low Voltage Directive
2011/65/CE RoHS Directive

Product Info

Product Description

Description

Power cable insulated with high-quality ethyl-propylene rubber, G7 quality, with PVC sheath, not propagating fire with reduced corrosive gas emission.

Conductor
Plain copper solid conductor, class 1 (section ≤ 6 mm2)
Plain copper stranded wire, class 2 (section ≥ 10 mm2)

Insulation
Rubber HEPR compound, G7 quality

Filler
Non-hygroscopic compound (for multi-core cables)

Outer Sheath
PVC compound, Rz quality

Cores Colour
HD 308 Standard

Sheath Colour
Grey

Technical Characteristics

Nominal voltage Uo/U: 0,6/1 kV

Maximum operating temperature: 90°C
Minimum operating temperature: -15°C
(without mechanical stress)

Minimum installation temperature: 0°C
Maximum short circuit temperature:
250°C up to 240 mm² section, over 220°C

Maximum tensile stress: 50 N/mm2
Minimum bending radius: 6 x maximum external diameter

Use and Installation

Power cable for industrial and/or residential uses. Suitable to be used indoor and outdoor, even in wet environments; it can be fixed on walls and/or metal structures. Suitable also for laying underground. (ref. CEI 20-67)